How to Ensure Easy Maintenance of Oil cooled transformers from China Manufacturers

1. Choose a reliable manufacturer: Make sure to choose a reputable manufacturer with a good track record of producing quality Oil cooled transformers. 2. Regular maintenance: Ensure that regular maintenance is carried out on the transformer, such as checking the oil levels, inspecting the wiring, and cleaning the cooling fins. alt-572 3. Use quality parts: Make sure to use quality parts when replacing any components of the transformer.
TypeRated capacity (KVA)No-load losses(W)Voltage combination (KV)Load losses(W)No-load current (%)Short-circuit impedance (%)
S11-M-30301006,6.3,10,10.5,11/0.46002.34.0
S11-M-50501306,6.3,10,10.5,11/0.48702.04.0
S11-M-63631506,6.3,10,10.5,11/0.410401.94.0
S11-M-80801806,6.3,10,10.5,11/0.412501.94.0
S11-M-1001002006,6.3,10,10.5,11/0.415001.84.0
S11-M-1251252406,6.3,10,10.5,11/0.418001.74.0
S11-M-1601602806,6.3,10,10.5,11/0.422001.64.0
S11-M-2002003406,6.3,10,10.5,11/0.426001.54.0
S11-M-2502504006,6.3,10,10.5,11/0.430501.44.0
S11-M-3153154806,6.3,10,10.5,11/0.436501.44.0
S11-M-4004005706,6.3,10,10.5,11/0.443001.34.0
S11-M-5005006806,6.3,10,10.5,11/0.451001.24.0
S11-M-6306308106,6.3,10,10.5,11/0.462001.14.5
S11-M-8008009806,6.3,10,10.5,11/0.475001.04.5
S11-M-1000100011506,6.3,10,10.5,11/0.4103001.04.5
S11-M-1250125013606,6.3,10,10.5,11/0.4128000.94.5
S11-M-1600160016406,6.3,10,10.5,11/0.4145000.84.5
S11-M-2000200022806,6.3,10,10.5,11/0.4178200.65.0
S11-M-2500250027006,6.3,10,10.5,11/0.4207000.65.0
S11-M-30-309020,22/0.46602.15.5
S11-M-50-5013020,22/0.496025.5
S11-M-63-6315020,22/0.411451.95.5
S11-M-80-8018020,22/0.413701.85.5
S11-M-100-10020020,22/0.416501.65.5
S11-M-125-12524020,22/0.419801.55.5
S11-M-160-16029020,22/0.424201.45.5
S11-M-200-20033020,22/0.428601.35.5
S11-M-250-25040020,22/0.433501.25.5
S11-M-315-31548020,22/0.440101.15.5
S11-M-400-40057020,22/0.4473015.5
S11-M-50050068020,22/0.4566015.5
S11-M-63063081020,22/0.468200.96
S11-M-80080098020,22/0.482501.86
S11-M-10001000115020,22/0.4113300.76
S11-M-12501250135020,22/0.4132000.76
S11-M-16001600163020,22/0.4159500.66
4. Use a qualified technician: Have a qualified technician inspect the transformer regularly to ensure that it is in good working order. 5. Follow the manufacturer’s instructions: Make sure to follow the manufacturer’s instructions for maintenance and operation of the transformer.