When selecting a ground mounted Power transformer for your factory, it is important to consider several factors. First, you must determine the power requirements of your factory. This includes the voltage and current levels that will be needed to power the equipment and machinery. Once you have determined the power requirements, you can then select a transformer that is capable of providing the necessary power. Next, you must consider the size and weight of the transformer. Ground mounted Power transformers come in a variety of sizes and weights, so it is important to select one that is appropriate for your factory. Additionally, you should consider the environmental conditions in which the transformer will be installed. This includes the temperature, humidity, and other environmental factors that could affect the performance of the transformer. Finally, you should consider the cost of the transformer. Ground mounted Power transformers can be expensive, so it is important to select one that is within your budget. Additionally, you should consider the warranty and maintenance requirements of the transformer. This will help ensure that the transformer will provide reliable power for your factory for many years to come. alt-844
By considering these factors, you can select the right ground mounted Power transformer for your factory. With the right transformer, you can ensure that your factory has the power it needs to operate efficiently and safely.

Fire-Proofing Your Ground Mounted Power transformer: What You Need to Know

TypeRated capacity (KVA)Voltage combination(KV)No-load losses(W)Load losses(W)No-load Current (%)Short-circuit impedance (%)
SH15-M-30306,6.3,10,10.5,11/0.4336301.504.0
SH15-M-50506,6.3,10,10.5,11/0.4439101.204.0
SH15-M-63636,6.3,10,10.5,11/0.45010901.104.0
SH15-M-80806,6.3,10,10.5,11/0.46013101.004.0
SH15-M-1001006,6.3,10,10.5,11/0.47515800.904.0
SH15-M-1251256,6.3,10,10.5,11/0.48518900.804.0
SH15-M-1601606,6.3,10,10.5,11/0.410023100.604.0
SH15-M-2002006,6.3,10,10.5,11/0.412027300.604.0
SH15-M-2502506,6.3,10,10.5,11/0.414032000.604.0
SH15-M-3153156,6.3,10,10.5,11/0.417038300.504.0
SH15-M-4004006,6.3,10,10.5,11/0.420045200.504.0
SH15-M-5005006,6.3,10,10.5,11/0.424051400.504.0
SH15-M-6306306,6.3,10,10.5,11/0.432062000.304.5
SH15-M-8008006,6.3,10,10.5,11/0.438075000.304.5
SH15-M-100010006,6.3,10,10.5,11/0.4450103000.304.5
SH15-M-125012506,6.3,10,10.5,11/0.4530120000.204.5
SH15-M-160016006,6.3,10,10.5,11/0.4630145000.204.5
SH15-M-200020006,6.3,10,10.5,11/0.4750183000.205.0
SH15-M-250025006,6.3,10,10.5,11/0.4900212000.205.0