Resin insulation in Dry type transformers has become increasingly popular in recent years due to its numerous benefits. These transformers are widely used in various industries and applications, thanks to their efficiency, reliability, and safety features. In this article, we will explore the advantages of using resin insulation in Dry type transformers and why they are a preferred choice for many users.
One of the key benefits of resin insulation in Dry type transformers is its excellent thermal conductivity. The resin material used in these transformers has high thermal conductivity, which helps in dissipating heat more effectively. This ensures that the transformer operates at optimal temperatures, reducing the risk of overheating and improving its overall efficiency. Additionally, resin insulation is also resistant to temperature fluctuations, making it a reliable choice for applications that require consistent performance in varying environmental conditions.
Type
Rated capacity (KVA)
Voltage combination(KV)
No-load losses(W)
Load losses(W)
No-load current (%)
Short-circuit impedance (%)
SCH15-30
30
6,6.3,6.6,10,11/0.4
70
710
1.6
4.0
SCH15-50
50
6,6.3,6.6,10,11/0.4
90
1000
1.4
4.0
SCH15-80
80
6,6.3,6.6,10,11/0.4
120
1380
1.3
4.0
SCH15-100
100
6,6.3,6.6,10,11/0.4
130
1570
1.2
4.0
SCH15-125
125
6,6.3,6.6,10,11/0.4
150
1850
1.1
4.0
SC(B)H15-160
160
6,6.3,6.6,10,11/0.4
170
2130
1.1
4.0
SC(B)H15-200
200
6,6.3,6.6,10,11/0.4
200
2530
1.0
4.0
SC(B)H15-250
250
6,6.3,6.6,10,11/0.4
230
2760
1.0
4.0
SC(B)H15-315
315
6,6.3,6.6,10,11/0.4
280
3470
0.9
4.0
SC(B)H15-400
400
6,6.3,6.6,10,11/0.4
310
3990
0.8
4.0
SC(B)H15-500
500
6,6.3,6.6,10,11/0.4
360
4880
0.8
4.0
SC(B)H15-630
630
6,6.3,6.6,10,11/0.4
420
5880
0.7
4.0
SC(B)H15-630
630
6,6.3,6.6,10,11/0.4
410
5960
0.7
6.0
SC(B)H15-800
800
6,6.3,6.6,10,11/0.4
480
6960
0.7
6.0
SC(B)H15-1000
1000
6,6.3,6.6,10,11/0.4
550
8130
0.6
6.0
SC(B)H15-1250
1250
6,6.3,6.6,10,11/0.4
650
9690
0.6
6.0
SC(B)H15-1600
1600
6,6.3,6.6,10,11/0.4
780
11730
0.6
6.0
SC(B)H15-2000
2000
6,6.3,6.6,10,11/0.4
1000
14450
0.5
6.0
SC(B)H15-2500
2500
6,6.3,6.6,10,11/0.4
1200
17170
0.5
6.0
Another advantage of resin insulation in Dry type transformers is its superior dielectric strength. The resin material used in these transformers has excellent electrical insulation properties, which help in preventing electrical breakdowns and ensuring safe operation. This is particularly important in applications where high voltage levels are involved, as it helps in maintaining the integrity of the electrical system and reducing the risk of short circuits or other electrical faults.
In addition to its thermal and electrical properties, resin insulation in Dry type transformers also offers excellent mechanical strength. The resin material used in these transformers is highly durable and resistant to mechanical stress, making it a reliable choice for applications that require robust and long-lasting equipment. This ensures that the transformer can withstand the rigors of daily operation without compromising its performance or reliability.
Furthermore, resin insulation in Dry type transformers is also known for its low maintenance requirements. The resin material used in these transformers is resistant to moisture, chemicals, and other environmental factors, reducing the need for frequent inspections and repairs. This not only saves time and resources but also ensures that the transformer operates efficiently for an extended period, providing long-term benefits to users.
Moreover, resin insulation in Dry type transformers is also environmentally friendly. The resin material used in these transformers is non-toxic and recyclable, making it a sustainable choice for users who are conscious of their environmental impact. This aligns with the growing trend towards green technologies and sustainable practices, making resin insulation in Dry type transformers a preferred choice for environmentally conscious users.
In conclusion, resin insulation in Dry type transformers offers a wide range of benefits, including excellent thermal conductivity, superior dielectric strength, high mechanical strength, low maintenance requirements, and environmental sustainability. These transformers are a reliable and efficient choice for various applications, providing users with a safe and reliable electrical solution. With fast delivery options available from reputable exporters and makers, resin insulation in Dry type transformers is a cost-effective and practical choice for users looking for high-performance electrical equipment.
Jak wybrać odpowiedni Transformator mocy średniego napięcia do swojego zastosowania: przewodnik dla producentów charakteryzujących się niskim poziomem hałasu Przy wyborze Transformatora…
Badanie zalet Transformatorów zanurzonych w cieczy do regulacji napięcia bez obciążenia Szukasz sposobu na poprawę regulacji napięcia w układzie elektrycznym w…
Korzyści ze stosowania Transformatorów zanurzonych w oleju typu uszczelnionego Transformatory zanurzone w oleju typu uszczelnionego są popularnym wyborem w wielu gałęziach…
Zrozumienie zalet Transformatorów suchych chłodzonych powietrzem od producenta z Chin Transformatory suche chłodzone powietrzem pochodzące od chińskiego producenta oferują szereg korzyści…